Features
– 8 channels for 0… .20 mA, 4… .20 mA, 0… .5 V or 1… .5 V d.c. single-ended unipolar inputs.
– 1 group of 8 channels isolated from ground.
– 12-bit resolution.
– Transmitter supply current limited per channel.
– HART direct communication.
AI815 Analogue Input Module
The AI815 analogue input module has 8 channels.
The module can be configured as a voltage or current input. Current and voltage signals cannot be mixed on the same I/O module.
The voltage and current inputs can withstand overvoltage or undervoltage of at least 11 VDC.
Input resistance is greater than 10 M ohms for voltage inputs and 250 ohms for current inputs.
The module distributes external HART-compatible transmitter power to www.abb-drive.com each channel.
This adds a simple connection for power distribution to 2-wire or 3-wire transmitters. Transmitter power is monitored and current limited.
If an external power supply is used to power HART transmitters, the power supply must be HART-compatible.
The module cycles through self-diagnostics.
Module diagnostics include
– External power, transmitter power, and external shunt errors. These errors are reported as external channel errors.
– Analogue readback, reference voltage, internal power supply, checksum, watchdog, and memory. These errors are reported as module errors.
All eight channels are isolated from the module bus as a group. Power to the input stages is converted from the 24 V supply on the module bus.
The module has HART pass-through capability. Only point-to-point communication is supported.
Eight different types of MTUs can be used; the TU830/TU833 Extended MTU allows a three-wire connection to the device without additional terminals.
The TU810 (or TU814) Compact MTU has 24 V process voltage input terminals, but requires external terminals to distribute 24 V power to field devices.
The Extended MTUs, TU835 and TU838 provide one fuse per channel (3 A maximum) for external transmitter power.
The TU818 Compact MTU can be connected to 2-wire transmitters without external commissioning.
The TU812 Compact MTU has a D-Sub 25-pin (male) connector for process connection.
If HART is used, a shielded field cable for process connection is required.
The parameter shunt mode should be set to internal shunt when a current input is required and external shunt when a voltage input is required.
Features AI815 Analogue Input Module
Number of channels 8
Input type Unipolar single-ended
Measuring range 0…. .20 mA, 0… .5 V, 4… .20 mA, 1… .5V 5V
Overrange +15
Input impedance (voltage input) 10 MΩ
Input impedance (at current input) (including PTC) 250 Ω
Maximum field cable length 600 metres (656 yards)
Voltage input, maximum lossless 11 V DC NMRR, 50 Hz, 60 Hz > 40 dB
Maximum error 0.1%
Resolution 12 bits
Maximum temperature drift 50 ppm/°C
Update cycle time 10 ms
Current consumption 24 V (module bus) 50 mA
Current consumption 5 V (module bus) 100 mA
Current consumption 24 V (process power supply, UPx) 339 mA (max) (22 mA + transmitter current * 1.32)
Power dissipation 3.5 W
Transmitter power supply HART compatible
Voltage: 24 V @ 23 mA
Current: 30 mA + – 10%(1)
Monitoring module error if: Analogue readback,
reference voltage, internal power supply,
Checksum, watchdog, and memory errors
External channel error if: external power supply
External power supply low, transmitter power supply error
Input filter (rise time 0-90%) 290 ms
Isolation Configuration Ground Isolation
Module Terminal Unit TU810. TU812. TU814. TU818. TU830.
TU833. TU835. or TU838
MTU keying code CC
Rated insulation voltage 50 V
Insulation test voltage 500 V (AC)