The 16-channel output relay module is designed for high reliability of the plant’s most critical rotating machinery.
This 2-slot monitor is used with the AMS 6500 to form a complete API 670 machinery protection monitor.
Applications include steam, gas, compressor and hydraulic turbine machinery.
Any channel clear, alarm or warning signal can be selected as an input to the 16 channel output relay module.
Uses Boolean logic, applies time delays and selects output relays
Easy-to-use software provides a graphical logic display that graphically guides the www.abb-drive.com user through the configuration.
The AMS 6500 Machinery Health Monitor is an integral part of PlantWeb® and AMS software.
PlantWeb provides comprehensive machinery health operation in conjunction with the Ovation® and DeltaV™ process control systems.
AMS software provides maintenance personnel with advanced predictive and performance diagnostic tools, enabling them to determine machine failures early with confidence and accuracy.
3U-sized 2-slot plug-in module reduces cabinet space requirements by half compared to traditional 6U cards
API 670 compliant, hot-swappable modules
60 inputs, 30 logic expressions, 16 relay outputs
6740 is a 12TE wide module for IMR6000 series racks
6740-10 is a 10TE wide module for IMR6500 series racks
Data Outputs
Relays
Configurable redundant relays Data Outputs
Configurable redundant relays
Mechanical relays, API 670 compliant
Specifications Control Voltage: 13-32
VDC Contact Load: 48 V, 1 A Normally open or normally closed, selectable
Normally open or normally closed, selectable
Normally open or normally closed, selectable
Single Pole Double Throw (SPDT), Optional
Double Throw (SPDT)
Configurable Redundant Relay Off, Double Throw (SPDT)
Configurable redundant relays Off,
AND, OR, Triple Choice, AND AND OR Up to 30 logic expressions can be defined per relay.
Each
6740 Module
Inputs
60 input types:
Channel Zero (slot number),
Channel 1 and 2
Alarm (slot number), channels 1 and 2
Danger (slot number),
Channel 1 and 2
Outputs:
Relay 1 – 16
Time Delay
0 – 30 seconds
Handle
Easily removes card and provides board
for module identification
Environment, general
Module IP 00. DIN 40050
Front plate IP 20. DIN 40050
Climate DIN 40040 KTF class
Operating temperature 0° – 65°C (32° – 149°F)
Storage and transport temperature -40° – 70°C (-40° – 158°F)
Relative humidity 5 – 95%, non-condensing
Vibration
– Vibration
– Acceleration
IEC 68-2. Part 6
0.15 mm, 10 – 55 Hz
19.6 mm/s2. 55 – 150 Hz
Shock
– Shock duration
IEC 68-2. Part 29
98 m/s2 (9.98 g peak)
16 ms
Electromagnetic compatibility EN50081-1 / EN50082-2
Maximum power consumption 6 W
Configuration Password protected
6740 Relay
Module dimensions:
PCB/EURO card format according to DIN 41494. 100 x 160 mm (3.937 x 6.300 in)
Width: 60 mm (2.362 in) (12 TE)
Height: 128.4 mm (5.055 in) (3 HE)
Length: 160 mm (6.300 in)
Net weight: approx. 320 g (0.705 lb)
Gross weight: approx. 450 g (0.992 lb)
Package volume: approx. 2.5 cubic metres (0.08 cubic feet)
6740-10 Relay
Module dimensions:
PCB/EURO card format to
DIN 41494 standard, 100 x 160 mm (3.937 x 6.300 in)
Width: 54.46 mm (1.99 in) (10 TE)
Height: 128.4 mm (5.055 in) (3 HE)
Length: 160 mm (6.300 in)
Net weight: approx. 320 g (0.705 lb)
Gross weight: approx. 450 g (0.992 lb)