GENERAL
The Honeywell EC/RM7830. EC/RM7850 Relay Module is a microprocessor-based integrated burner control for automatically fired gas, oil, or combination fuel burner on/off (EC/RM7830A) or full modulation (EC/RM7850A) power burner applications. The EC/RM7830A or EC/RM7850A system consists of the relay module, wiring subbase, amplifier and purge card. Options include the keyboard display module (KDM), personal www.abb-drive.com computer interface, Data ControlBus™ Module, and Combustion System Manager® Software. The KDM can be mounted on the relay module or on the face of a panel door. The KDM can also be remotely mounted from the panel if this is approved for the application.
The EC/RM7830. EC/RM7850 is programmed to provide a level of safety, functional capability and features beyond the capacity of conventional controls.
The basic functions of the EC/RM7830A, EC/RM7850A includes automatic burner sequencing, flame supervision, system status indication, system or self-diagnostics, and troubleshooting.
FEATURES
• Safety Features:
— Interlock check.
— Dynamic Ampli-Check™.
— Closed loop logic test.
— Dynamic input check.
— Dynamic safety relay test.
— Dynamic self-check logic.
— High Fire Purge Switch test (EC/RM7850A).
— Expanded safe-start check.
— Internal hardware status monitoring.
— Low Fire Start Switch test (EC/RM7850A).
— Tamper-resistant timing and logic.
• Ignition attempts: 1 or 5. Selectable by model number.
• Access for external electrical voltage checks.
• Application flexibility.
• Microcomputer technology allows dependable, long-term operation.
• First-out annunciation and system diagnostics provided by a 2-row by 20-column vacuum fluorescent display (VFD) located on the KDM (optional). Text readout available in English, Spanish, Portuguese, French, German, Japanese (Katakana), Chinese, and Italian languages.
• Five sequence information light emitting diodes (LEDs) with symbols for Power, Pilot, Flame, Main, and Alarm (see Fig. 1).
• Five-function Run/Test Switch.
• Interchangeable plug-in flame amplifiers.
• Non volatile memory; EC/RM7830A, EC/RM7850A retain history files and sequencing status after the loss of power.
• Remote reset (subject to application approval; optional).
• Remote mounting of KDM (subject to application approval).
• Burner control data available on the optional KDM:
— Flame signal strength.
— Hold status.
— Lockout/alarm status.
— Sequence status.
— Sequence time.
— Total cycles of operation.
— Total hours of operation.
— Fault history providing the six most recent faults:
• Cycles of operation at the time of the fault.
• Fault message and code.
• Hours of operation at the time of the fault.
• Sequence status at the time of the fault.
• Sequence time at the time of the fault.
— Diagnostic information:
• Device type.
• Flame amplifier type.
• Flame failure response time (FFRT).
• Manufacturing code.
• On/off status of all digital inputs and outputs.
• Selected prepurge time.
• Software revision and version of relay module and optional KDM.
• Status of configuration jumper.
• Status of Run/Test Switch.