Features
” From the Vibro-Meter® product family
” Relay card with screw terminal block
” 16 relays with changeover contacts
” Relay-driven inverted logic (jumper selectable)
” Low contact resistance
” Low capacitance
” High throughput power
” Real-time board insertion and removal (hot-swappable)
” EU EMC compliance
Description of the RLC16 Relay Card
The RLC16 relay card is designed for use in Meggitt Sensing Systems’ VM600 Series Vibrometer® www.abb-drive.com roduct line for mechanical protection systems as well as condition and performance monitoring systems.
It is an optional card for use when the four relays on the IOC4T I/O card are insufficient for the application and additional relays are required.
The RLC16 is mounted on the rear of the VM600 (ABE04x) rack and connects directly to the rack backplane via a connector.
The RLC16 contains 16 relays with changeover contacts. Each relay is associated with 3 terminals on the screw terminal strip at the rear of the VM600 rack.
The relays are controlled by software-controlled open collector actuators.Jumpers on the RLC16 card allow selection of either Normal Energized (NE) or Normal De-energized (NDE) relays.
Relay Characteristics
Relay Name: RL1 to RL16
Type: PE014005
Contact Arrangement: 1 COM, 1 NC, and 1 NO contact/relay.
All relay contacts are on J1. J2 and J3.
Rated voltage: 250 VAC
Current Rating: 5 AAC
Maximum breaking capacity (no contact protection): 1250 VA
Maximum DC Load Breaking Capacity Curve
Operate/Release/Return Time: Typically 8 / 8 / 6 milliseconds
Dielectric strength test voltage
– Between open contacts: 1000 VAC
– Between contacts and coil: 4000 VAC
Mechanical life: 15 x 106 operations
Electrical life: >105 operations
Display: 16 relay PCBs
Relay status: Normal energized or normal de-energized (jumper optional)
External connections : Screw terminal connectors (J1. J2 and J3)
Mounting: Mounted on the rear of the VM600 rack and connected to the rack’s backplane via connectors. Rack Backplane
Temperature Range: See Relay Characteristics above
Humidity: ≤95% (non-condensing relative humidity)
RLC16 Power Supply
Supply voltage: +5 VDC
Consumption: 40 mA x 16 (per relay)
ENVIRONMENT
Operating environment
– Temperature : -25 to +65°C (-13 to +149°F)
– Humidity: 0 to 90% non-condensing
Storage
– Temperature : -40 to +85°C (-40 to +185°F) -40 to +85°C (-40 to +185°F)
– Humidity: 0 to 95% non-condensing
Vibration and shock: See general specifications for VM600 racks
Physical Dimensions
Height: 6U (262 mm, 10.3 inches)
Width: 20 mm (0.8 in)
Depth: 125 mm (4.9 in)
Weight: 0.30 kg (0.66 lbs)
Translated with DeepL.com (free version)